Good quality Main Switch Disconnector - 12kV Indoor High Voltage Combined Load Earthing Switch for Switchgear – Aiso Detail:
Switch Product Description
Jn15 indoor high-voltage alternating-current earthing switch is used as a support product for indoor three-phase alternating- current power systems of 3 ~ 40.5kV and 50(60)Hz and high- voltage switch cabinets or as an earthing switch for the overhauls of high-voltage electrical equipment. It is characterized by simple and compact structure, light weight, flexible operation, easy installation and good thermal stability and dynamic stability.
JN15-12/24/40.5KV indoor high-voltage alternating-current earthing switch is produced in line with the following standards and codes.
GB 1985 High-voltage alternating-current disconnectors and earthing switchesIEC 62271-102 High-voltage alternating-current disconnectors and earthing switches
High Voltage Combined Earthing Switch Environmental Conditions Ambient temperature: – 40°C~+40°C (below 35°C within 24 hours) Relative humidity: ≤95% (daily average) or ≤90% (monthly average)
Altitude: ≤ 1000m
Grounding Switch Main Technical Parameters
Item |
Unit |
Rsference valie |
Rated voltage |
KV |
12/24/40.5 |
Rated insulation level |
Lightning impulse withstand voltage |
KV |
75,145,185 |
1min power-frequency withstand voltage |
KV |
42,65,95 |
Rated frequency |
Hz |
50 / 60 |
Rated short-time withstand current |
kA |
31.5 / 40 |
Rated withstand current(peak value) |
kA |
80 / 100 |
Interphase center distance |
mm |
See the table |
Note:Please contact the factory to confirm the latest parameters
Outline and installation dimension
Model and specification |
E |
L |
C |
JN15-12/40-150 |
150 |
540 |
396 |
JN15-12/40-210 |
210 |
655 |
516 |
JN15-12/40-230 |
230 |
710 |
556 |
JN15-12/40-250 |
250 |
760 |
596 |
JN15-12/40-275 |
275 |
810 |
646 |
Product picture details (Real product picture, unprocessed)
Service Environment
Product detail pictures:
Related Product Guide:
Our organization promises all customers with the first-class products and solutions and the most satisfying post-sale service. We warmly welcome our regular and new clients to join us for Good quality Main Switch Disconnector - 12kV Indoor High Voltage Combined Load Earthing Switch for Switchgear – Aiso, The product will supply to all over the world, such as: Uganda, Tanzania, UK, Our products are exported worldwide. Our customers are always satisfied with our reliable quality, customer-oriented services and competitive prices. Our mission is "to continue to earn your loyalty by dedicating our efforts to the constant improvement of our products and services in order to ensure the satisfaction of our end-users, customers, employees, suppliers and the worldwide communities in which we cooperate".