Dry Type Current Transformer Summary
LFZB8-6,10(A,B) current transformer adopts the structure of epoxy resin vacuum casting full-seal transfixion, it is applied to testing the current & power and protecting on the relay in the indoor power system with rated frequency 50Hz, and rated voltage 10kV and below. Specially replaces old products such as LA-10, LAJ-10, LFZ1-10,LFZ2-10, LFZJ1-10, LFZS-10,LFZ-10G etc, in order to bring the convenience for installation, its one-time connection way is designed into A style and B style, and may be selected according to requirements.
Type designation
Technical parameter
Rated primary current(A) | 15 | 20 | 30 ,40 | 50, 60 | 75 | 100 | 150 ,200 | 300, 400 | 500 ,600 | 800 | 1000 |
One-second-thermal current(KA virtual value) | 2 | 3 | 5 | 10 | 16 | 20 | 31.5 | 40 | 63 | 80 | 100 |
Dynamic stable current(KA virtual value) | 5 | 7.5 | 12.5 | 25 | 40 | 50 | 78 | 100 | 157 | 200 | 250 |
Outline and installation dimension