Summary
It is suitable for JDZW-10R fully enclosed in sulated voltage transformer(hereinafter referred to as transformer er). Transformer is outdoor device, it is built-in with fuse to be used in power system with rated frequency of 50Hz/60Hz and rated voltage of 10KV for electrical measurements, protection and power supply.
Working conditions
1.System grounding method
Neutral point non-effective grounding system
2.Standard
No. | Name | Unit | Parameter | |
1 | Ambient temperature(outdoor) | Maximum temperature | ℃ | 40 |
Minimum temperature | ℃ | -30 | ||
Maximum daily temperature difference | K | 30 | ||
2 | Altitude | m | ≥1500 | |
3 | Solar radiation intensity | W/cm2 | 0.1 | |
4 | Ice thickness | mm | 10 | |
5 | Wind speed and wind pressure | m/sPa | 34/700 | |
6 | Maximum wind speed(from the ground heigh 10M, to maintain the average maximum of 10min | m/s | 35 | |
7 | Humi dity | Average relative humidity | % | ≤95 |
Average monthly relative humidty | ≤90 | |||
8 | Earthquake resistant capacity | Horizontal acceleration | g | 0.3 |
Ground vertical acceleration | 0.15 | |||
Safety factor | / | 1.67 |
Technical parameters
Type | Rated frequency(Hz) | Rated voltage ratio (V) | Accuracy class | Rated output(VA) | Ultimate output(VA) | Rated insulation leve(kV) |
JDZW-6R | 50-60 | 6000/220 | 3 | 500 | 1000 | 7.2/32/60 |
JDZW-10R | 50-60 | 10000/220 | 3 | 500 | 1000 | 12/42/75 |
JDZW-6R | 50-60 | 600/100/220 | 0.5/3 | 30/500 | 1000 | 7.2/32/60 |
JDZW-10R | 50-60 | 10000/100/220 | 0.5/3 | 30/500 | 1000 | 12/42/75 |
Type designation
Outline and installation dimension