LW8A Outdoor High Voltage SF6 Circuit Breaker With Good Quality

Short Description:

Specification:500-6000 USD/PIECEUse Parts:1 PIECESupply Ability:100 PIECEPayment Terms:TT , LC , Others Tags:


Product Detail

Product Tags

Place of OriginZhejiang, ChinaBrand NameAISO/OEMModel NumberLW8A-40.5TypeHigh Voltage, Outdoor High Voltage Circuit BreakerPoles Number3ProductSF6 Circuit BreakerRated Voltage40.5kVRated current1600/2000ARated frequency50HzMechanical life10000TimesAltitude≤2000mWeightAbout1000KgCustomizedAccept special orderPortNingbo/ShanghaiPackaging DetailsStandard export wooden case packingPortNingbo or Shanghai

Quick Reply Professional Consultation Continued Cooperation

Application

Actastheprotectingandcontrollingunitforgridequipmentsandindustrialminingenterprises’equipments,LW8A-40.5 type outdoor SF6 circuit breaker is an outdoor device used in AC 50HZ three-phase 40.5KV power system.It is applicable to locations that need frequent operating in rated current or under repeatedly on/off short circuit current. Containing the current transformer for measurement and protection, it can directly replace SW2-35 less oil circuit breaker and various types of oil circuit breaker with transition bracket. It can also be used as a tie breaker and switching capacitor group situations with CT14 type spring mechanism.

Standards

GB1984

GB/T28001-2011 idt OHSAS18001:2007

GB/T24001-2004 idt ISO14001:2004

Features

Excellent breaking performance, short burning arc time, long life;

Mechanical life of more than 3000 times;

Operation frequently, each can be installed 12 current transformers;

New type SF6 MKZ pointer type density meter, pressure gauge reading is not affected by temperature changes;

Environmental Condition

Ambienttemperature:-30℃~+40℃

Altitude:≤3000m

Wind pressure:≤700Pa

Relative humidity:daily average relative humidity: ≤95%;monthly average relative humidity≤90;daily average saturated vapor pressure ≤2.2KPa;monthly average value ≤1.8KPa

Air pollution level:Ⅲ

Earthquake intensity:≤8 degree

The installation should be free from fire, explosion, severe vibration, chemical corrosion and serious pollution

Type designation

212

Main technical data

No. Item Unit Data
1 Ratedvoltage KV 40.5
2 Ratedcurrent A 2000
3 Ratedfrequency HZ 50
5 Ratedshortcircuitbreakingcurrent KA 31.5
6 Ratedshort-circuitcurrent(peak) KA 50
7 Ratedshort-circuitwithstandcurrent KA 20
10 Ratedshortcircuitclosingcurrent(peak) KA 50
13 Electricallifeofratedshortcircuitbreakingcurrent times 30
14 Ratedshortcircuitduration s 4
15 Ratedlinechargingclosecurrent A 31.5
16 Ratedoperationsequence O-0.3s-CO-180s-CO
17 Splittime ms ≤60
18 Closingtime ms ≤100
19 Velocityofrigidcomposite m/s 3.2
20 Velocityofrigidity m/s 3.4
21 Mechanicallife times 6000
24 Qualityofeachcircuitbreaker kg 1400

Outline and installation

cccc

cvdvdvd