Place Of Origin:Hangzhou,China
General Description
ZW8-12 Series outdoor high voltage vacuum circuit breaker is main switch equipment of rated voltage 12KV, three phases AC50Hz system, to switch on/off loading current, over-current, and short circuit in rural or urban power network. The structure of breaker is of three-phase assembled in a tank, three-phase vacuum arc-extinguishing chamber enclosed in metal tank, insulation material between phases and phase to each made of SMC, reliable performances, and high insulating strength.
ZW8-12G consists of ZW8-12 breaker and isolator, called combined breaker, can be used as sectionalizer.
The operating mechanism for this series breaker is CT23 spring charging mechanism, motor or hand operating type.
Main Technical Parameters
Item |
Description |
Data |
|
1 |
Ratedvoltage(KV) |
12 |
|
2 |
Max.voltage(KV) |
12 |
|
3 |
Ratedcurrent(A) |
630 |
|
4 |
Ratedshortcircuitloadbreakingcurrent(KA) |
20 |
|
5 |
Ratedshortcircuitmakingcurrent(peak)(KA) |
50 |
|
6 |
Ratedpeakwithstandcurrent(KA) |
50 |
|
7 |
Rated1minwithstandcurrent(KA) |
20 |
|
8 |
Ratedinsulationlevel(KA) |
Powerfrequencywithstandvoltage(dry) |
42 |
Lightningimpulsewithstandvoltage(peak) |
75 |
||
9 |
Ratedoperatingsequence |
O-0.3s-CO-180s-CO |
|
10 |
Mechanicallife(times) |
10000 |
|
11 |
Nosofbreakingratedshortcircuitbreakingcurrent(times) |
30 |
|
12 |
Ratedclosebrakevoltageofoperatingmachnie(V) |
110,220 |
|
13 |
Ratedopeningbrakecurrentofoperatingmachine(V) |
110,220 |
|
14 |
Openingdistanceofcurrent(mm) |
11±1 |
|
15 |
Overtravelingdistance(springcompressedlenghtofcontact)(mm) |
3 |
|
16 |
Asynchronyofopeningorclosingthreephases(ms) |
≤2 |
|
17 |
Thejumptimeofcontactclosebreak(ms) |
≤2 |
|
18 |
Averagebreakspeed(s) |
1.0±0.2 |
|
19 |
Averageclosingspeed(s) |
0.7±0.15 |
|
20 |
Openingtime(s) |
Ubdermax.operatingvoltage |
0.015-0.05 |
Undermin.operatingvoltage |
0.03-0.06 |
||
21 |
Closingtime(s) |
0.025-0.05 |
|
22 |
Maincircuitresistanceofeachphase(μΩ) |
≤120 |
|
23 |
Permissibleabradedthicknessofmovingandstaticcontacts(mm) |
3 |
Note:Please contact the factory to confirm the latest parameters