1.Small size,Light weight,resistance to impact,no collision damage during transportation,flexible installation,suitable for use inthe switch cabin.
2.Special structure,the overall compression molding,no air gap,good sealing performance,moisture-proofand explosion-proof.
3.Large creepage distance,good hydrophobicity,strong stain resistance,stable performance and reduceoperation maintenance.
4.Unique formula of zinc oxide varistor, small leakage current,slow aging,long service life.
5.With DC reference voltage,rectangular flow capacity and high current and large current withstand capacity are higher than standard requirement.
Power frequency:48Hz ~60HzAmbient temperature:-40°C~+40°CMaximum wind speed: not exceed 35m/sAltitude: not exceed 2000mEarthquake intensity: not exceed 8 degreesIce thickness: not exceed 10 meters.Long-term applying voltage does not exceed the maximum coutinuous operating voltage.
Type Specifications
Main Technical Parameters
Service condition |
System nominal voltage kV |
Continous operation voltage kV |
DCMin U1mA reference voltage kV≥ |
ResidualvoltagekV≥ |
Square wave current impulse withstand A |
High current impulse kA |
||
1/4μs Steep current impulse |
8/20μs Lightning current impulse |
30/60μs Switching current impulse |
||||||
5kA Substation (Z) |
3 | 3.2 | 7.2 | 14.5 | 13.5 | 11.5 | 200 | 65 |
6 | 4 | 14.4 | 31 | 27 | 23 | |||
6 | 8 | 14.4 | 31 | 27 | 23 | |||
10 | 13.6 | 24 | 51.8 | 45 | 38.3 | |||
35 | 23.4 | 73 | 154 | 134 | 114 | 400 | 100 | |
40.8 | 73 | 154 | 134 | 114 | ||||
42.2 | 73 | 154 | 134 | 114 | ||||
43.2 | 73 | 154 | 134 | 114 | ||||
66 | 67.2 | 121 | 254 | 221 | 188 | 600 | 100 | |
72.5 | 130 | 258 | 224 | 190 | ||||
75.5 | 134 | 270 | 234 | 198 | ||||
110 | 75 | 140 | 287 | 250 | 212 | 600 | 100 | |
78 | 145 | 299 | 260 | 221 | ||||
80 | 148 | 305 | 266 | 226 | ||||
84 | 157 | 323 | 281 | 239 | ||||
88.2 | 168 | 347 | 302 | 256 |